• 대한전기학회
Mobile QR Code QR CODE : The Transactions of the Korean Institute of Electrical Engineers
  • COPE
  • kcse
  • 한국과학기술단체총연합회
  • 한국학술지인용색인
  • Scopus
  • crossref
  • orcid
Title A Study on the Measurements of Discharge Parameters in Case of the Switching Impulse Breakdown of a Large Air Spacing
Authors 최영욱 ; 조연옥
Page pp.1290-1295
ISSN 1975-8359
Abstract The paper presents the measurement results on the parameters affecting the breakdown mechanism of a large air spacing under switching impulse voltages. Measured parameters are the velocities of leader channels, predischarge currents, electric charges injected into the rod-plane air gap and electric field intensities on the plane. For the 3m air gap under switching impulse voltages, the velocities of leader channel have been measured to be of 1cm/x10S0-6Ts - 5cm/x10S0-6Ts, electric field intensity of 2kv/cm, predischarge current of 1.2-1.6A, the charges injected into the air gap of 11-40x10S0-6TC for 400-887kV impulse voltages.