• 대한전기학회
Mobile QR Code QR CODE : The Transactions of the Korean Institute of Electrical Engineers
  • COPE
  • kcse
  • 한국과학기술단체총연합회
  • 한국학술지인용색인
  • Scopus
  • crossref
  • orcid
Title Evaluation of Damage from Reclosing Scheme for Power Transfromer
Authors 오정환(O, Jeong-Hwan) ; 윤상윤(Yun, Sang-Yun) ; 임성정(Im, Seong-Jeong) ; 김재철(Kim, Jae-Cheol)
Page pp.177-183
ISSN 1975-8359
Keywords Reclosing Scheme ; Power Transformer ; Fault Current ; Cumulative Damage
Abstract This paper presents how to evaluate the transformer damage caused by reclosing scheme at the distribution substation. We describe a quantitative relationship between the reclosing scheme and the number of fault current flowing through transformer wsing the probability of a reclosing success/failure. The transformer damage from reclosing scheme is presented using a weight function and a damage function. A weight function is associated with the number of reclosing attempts and the reclosing deadtime to consider cumulative stress caused by reclosing scheme. A damage function is associated with a transformer impact ratio and a transformer functional life. In the case study, the transformer damage is simulated for the probability of a reclosing success. And the evaluation of transformer damage using KEPCO's operation data is performed.