Title Analysis and Estimation of the Transient Thermal Characteristics of OF Cable systems
Authors 강지원(Kang, Ji-Won) ; 이동일(Lee, Dong-Il) ; 정채균(Jung, Chae-Kyun) ; 이종범(Lee, Jong-Beom)
Page pp.487-495
ISSN 1975-8359
Keywords OF Cable ; Transient Stat ; Thermal Model ; Temperature Characteristic ; Underground Power Cable System
Abstract This paper reviews the characteristic of thermal and temperature of oil field cable in transient state such as grounding fault and lightning surge. For analysis in various conditions, many actual underground power cable systems are modeled using ATP. These results are applied for the examination of temperature increase when the single line to ground fault by the breakdown of insulation part and hitting of lightning surge are occurred. The inner part temperature of OF cable is analysed according to the various kinds of cable using the thermal model of transient state. The temperature increase of sheath and crossbonded lead bv fault current is also analysed using IEC 60949.