Title A Study on SFCL Systems for Future Korean T&D Power System Application Considering Auto Reclosing Actions of Protection System
Authors 이승렬(Lee Seung Ryul) ; 김종율(Kim Jong-Yul) ; 윤재영(Yoon Jae Young)
Page pp.580-585
ISSN 1975-8359
Keywords 초전도한류기 ; 자동재폐로 ; 송배전계통 ; 보호협조 ;
Abstract The recovery time of developing SFCL(Superconducting Fault Current Limiter) has an uncertainty. In general, the recovery time is estimated at 1 sec and more, even though the progress of SFCL technology is considered. However, auto reclosing time of circuit breaker is 0.3 or 0.5 sec in Korean power system. It is impossible to apply only one SFCL to power system because the recovery time is over the reclosing time of protection system. This study proposes two new SFCL systems for power system application. The proposed systems consider auto reclosing action for the protection in practical power system and consist of tow parallel SFCLs.