• 대한전기학회
Mobile QR Code QR CODE : The Transactions of the Korean Institute of Electrical Engineers
  • COPE
  • kcse
  • 한국과학기술단체총연합회
  • 한국학술지인용색인
  • Scopus
  • crossref
  • orcid
Title Comparison of Thermal Recovery Characteristics of Hybrid Type Model Gas Interrupters According to the Arrangement of Thermal Expansion Chamber and Puffer Cylinder
Authors 송기동(Song Ki-Dong) ; 정진교(Chong Jin-Kyo) ; 박경엽(Park Kyong-Yop)
Page pp.725-731
ISSN 1975-8359
Keywords Hybrid Interrupter ; Thermal Recovery ; Distortion of Stroke ; Thermal Expansion Chamber ; Puffer Cylinder
Abstract In this study, the three type hybrid interrupters according to the arrangement of the thermal expansion chamber and the puffer cylinder(they are called 'serial type', 'parallel/exchanged type', and 'parallel/separated type' respectively in this work) were designed and manufactured. This paper presents the tested results of the thermal recovery characteristics on the interrupters using a simplified synthetic test facility. The 'serial type' hybrid interrupter which is to obtain more easily the pressure rise for the thermal recovery compared with the others has the best capability in the thermal recovery characteristics. In order to investigate the stress on the operating mechanism, the distortion of the stroke wave in on-load test was examined to the stroke curve in no-load test. The biggest distortion was occurred in the 'parallel/exchanged type' hybrid interrupter. Finally, the small interruption capability on the three type interrupters was estimated by a theoretical form and the 'parallel/separated type' hybrid interrupter has the advantage of the others in the view of structure.