Title Comparison of Voltage Unbalance Factor for Line and Phase Voltage
Authors 김종겸(Kim Jong-Gyeum) ; 박영진(Park Young-Jeen) ; 이은웅(Lee Eun-Woong)
Page pp.403-407
ISSN 1975-8359
Keywords Unbalance Voltage ; Line-to-Line and Phase-to-Phase Voltage ; Voltage Unbalance Factor(VUF)
Abstract Most of the loads in industrial power distribution systems are balanced and connected to three power systems. However, voltage unbalance is generated at the user's 3-phase 4-wire distribution systems with single & three phase. Voltage unbalance is mainly affected by load system rather than power system. Unbalanced voltage will draws a highly unbalanced current and results in the temperature rise and the low output characteristics at the machine. It is necessary to analyse correct voltage unbalance factor for reduction of side effects in the industrial sites. Voltage unbalance is usually defined by the maximum percent deviation of voltages from their average value, by the method of symmetric components or by the expression in a more user-friendly form which requires only the three line voltage readings. If the neutral point is moved by the unbalanced load at the 3-phase 4-wire system. Line and phase voltage unbalance leads to different results due to zero-sequence component. So that it is difficult to analyse voltage unbalance factor by the conventional analytical method, This paper presents a new analytical method for phase and line voltage unbalance factor in 4-wire systems. Two methods indicate exact results.