Title An Application of the On Line Partial Discharge Measurement Method in Transformer
Authors 권동진(Kweon, Dong-Jin)
Page pp.394-400
ISSN 1975-8359
Keywords Transformer ; Partial discharge ; RIV ; Corona ; On line monitoring ; Noise gating method
Abstract This paper describes an application of the on line partial discharge measurement method in operating transformer. In the operating transformer, the partial discharge signal may be superimposed by radio intereference voltage(RIV) and pulse shaped noise signals generated by external corona. The partial discharge quantity showed about 3,800pC due to very high sinusoidal interferences at the measuring impedance terminal of the transformer bushing tap. In order to reject these noises, this paper applied RIV filter, band-pass filters and noise gating method. The resulting measuring sensitivity was improved from 3,800pC to 160pC.