• 대한전기학회
Mobile QR Code QR CODE : The Transactions of the Korean Institute of Electrical Engineers
  • COPE
  • kcse
  • 한국과학기술단체총연합회
  • 한국학술지인용색인
  • Scopus
  • crossref
  • orcid
Title Application of the Ultrasonic Detection System for the Power Transformer
Authors 권동진(Kweon, Dong-Jin) ; 구교선(Koo, Kyo-Sun) ; 김재철(Kim, Jae-Chul)
Page pp.553-557
ISSN 1975-8359
Keywords Ultrasonic ; Preventive Diagnosis ; Partial Discharge ; Power Transformer ; Location
Abstract This paper describes the application results of an ultrasonic detection system for the power transformer. The ultrasonic detection system with 6 sensors was applied to detect partial discharge in a 154kV transformer with a dangerous levels of C_{2}H_{2}, C_{2}H_4 and CH_{4} gases. The ultrasonic detection tests were carried out 2 times, respectively, to confirm the existence and location of the partial discharge in the transformer. As a result of internal inspection, the arc trace between the pressure ring and core due to the partial discharge was found at the estimated position based on the amplitude and arriving time of the ultrasonic signals. Therefore, it was verified that the ultrasonic detection system is effective as a preventive diagnosis method for the power transformer. Also, the reliability of the ultrasonic detection system in detecting partial discharges in the transformer was also confirmed. It is expected, therefore, that the ultrasonic detection system will have beneficial effects on applications and verifications in detecting partial discharges for the power transformer.