• 대한전기학회
Mobile QR Code QR CODE : The Transactions of the Korean Institute of Electrical Engineers
  • COPE
  • kcse
  • 한국과학기술단체총연합회
  • 한국학술지인용색인
  • Scopus
  • crossref
  • orcid
Title A Fault Indicator Generation Algorithm using Phase Angle of Zero-Sequence Current in Ungrounded System
Authors 임희택(Lim, Hee-Taek) ; 임일형(Lim, Il-Hyung) ; 최면송(Choi, Myeon-Song) ; 이승재(Lee, Seung-Jae)
Page pp.1141-1149
ISSN 1975-8359
Keywords Distribution System ; Distribution Automation ; Ungrounded System ; FI ; Fault Indicator ; Zero-Sequence Current
Abstract Most faults are single-phase-to-ground fault in ungrounded system. The fault currents of single-phase-to-ground are much smaller than detection thresholds of measurement devices, so detecting single-phase-to-ground faults is difficult and important in ungrounded system. This paper proposed to a FI(Fault Indicator) generation algorithm in ungrounded system. The algorithm just using line-to-line voltage and zero-sequence current detects fault line, fault phase, fault section and FI(Fault Indicator) at terminal device, This paper also proposed to application plan for this algorithm. In the case study, the proposed algorithm has been testified in demo system by Matlab/Simulink simulations.