Title Improvement of Detailed Fault Point Decision Using EMTP Analysis of Search Coil Method for HVDC Cables
Authors 정채균(Jung, Chae-Kyun) ; 박진우(Park, Jin-Woo) ; 양병모(Yang, Byeong-Mo) ; 강지원(Kang, Ji-Won) ; 이종범(Lee, Jong-Beom)
DOI https://doi.org/10.5370/KIEE.2011.60.9.1656
Page pp.1656-1662
ISSN 1975-8359
Keywords EMTP ; Fault location ; Search coil ; Submarine cable
Abstract In a previous paper, the EMTP modeling technique using search coil test is established through various transient analysis including system grounding condition and grounding resistance for HVDC submarine cables. It was also proved by comparison with real test results. Based on this EMTP modeling technique, in this paper, it will be applied for modeling of pm180kV real HVDC submarine system(Jeju~Haenam). This paper variously analyses the effects of fault resistance including the resistance between core and sheath, the resistance between sheath and amore and the resistance between amore and sea water through EMTP modeling of search coil method. The results can contribute to the accuracy of detailed fault point prediction of search coil test for HVDC submarine cables.