• 대한전기학회
Mobile QR Code QR CODE : The Transactions of the Korean Institute of Electrical Engineers
  • COPE
  • kcse
  • 한국과학기술단체총연합회
  • 한국학술지인용색인
  • Scopus
  • crossref
  • orcid
Title Review on tolerance factors for 1E UVR setting at NPPs
Authors 문수철(Moon, Su-Cheol) ; 김건중(Kim, Kern-Joong)
DOI https://doi.org/10.5370/KIEE.2012.61.3.367
Page pp.367-372
ISSN 1975-8359
Keywords UVR ; PT ; Tolerance factor ; 1E ; Dependant or independent
Abstract In nuclear plants, UVR (under voltage relay, 27r) of 1E bus, which protected and supplied power to essential loads, to safety trip of reactor and supplied to starting signal of EDG (emergency diesel generators) automatically. therefore UVR tolerances setting and calculation method has been important to nuclear facility. If calculation and tolerances values differ or ignore, may induced power loss and economical loss by protective failure. This paper show results for calculation methods, and whether dependant or independent methods for factors. included whether PT (potential transformer/voltage transformer) tolerance or not adapted, and based on UVR setting method within a difference minimum and maximum of rated voltage to safety operation in nuclear plants.