Title Analysis on the Protective Coordination with Hybrid Superconducting Fault Current Limiter
Authors 신호전(Shin, Ho-Jeon) ; 김진석(Kim, Jin-Seok) ; 박유환(Park, Yu-Hwan) ; 김재철(Kim, Jae-Chul) ; 조만영(Cho, Man-Young)
DOI https://doi.org/10.5370/KIEE.2012.61.4.503
Page pp.503-508
ISSN 1975-8359
Keywords Ground potential transformer ; Current limit resistor ; Grounding resistance system ; Burden
Abstract Among the high distribution voltage consumers, high-capacity consumers are often applying the grounding resistance method in order to overcome demerits such as erroneous operation of the ground reply or potential increase in the battery at the accident of the isolated neutral system. In this paper, to prevent damage to CLR and GPT in the delay to block the breakdown in the resistance grounded neutral system, this study aims to provide a proper suggestion for continuous rating capacity of GPT to check the appropriateness of CLR size and reduce GPT burden. Thereupon, this study comparatively analyzes CLR current applied in general GPT and the current gained when CLR demanded in the system is used and analyzes the simulated system through simulation using PSCAD/EMTDC in order to suggest GPT's proper continuous rating capacity.