• 대한전기학회
Mobile QR Code QR CODE : The Transactions of the Korean Institute of Electrical Engineers
  • COPE
  • kcse
  • 한국과학기술단체총연합회
  • 한국학술지인용색인
  • Scopus
  • crossref
  • orcid
Title Lightning Surge Analysis on Underground System in DC Combined Distribution System
Authors 안천용(An, Chun-Yong) ; 이종범(Lee, Jong-Beom)
DOI https://doi.org/10.5370/KIEE.2013.62.6.737
Page pp.737-743
ISSN 1975-8359
Keywords EMTP ; DC distribution system ; DC combined distribution system ; Lightning surge ; Overvoltage
Abstract This paper describes the overvoltage through lightning surge analysis on underground system in DC combined distribution systems. It is considered that operating micro grid including distributed generation with smart grid can make possibility of composing new distribution system different from existing one. However, there are many papers about low voltage DC distribution in grids or buildings but not many about replacement or distributing 22.9kV AC distribution system to DC system. Among many research need for DC system development, overvoltage is studied in this paper. Overvoltage is simulated on DC cable when lightning strikes to overhead grounding wire which is installed at the nearest location from power cable section. Analysis as well as modeling is performed in EMTP/ATPDraw. It is evaluated that analysis results can be used to design of DC underground distribution power cable system.