Title Analysis of Transient Characteristics of a SFCL Applied Into Third-winding Transformer in a Single Line-to-ground Fault
Authors 최혜원(Choi, Hye-Won) ; 최효상(Choi, Hyo-Sang) ; 정병익(Jung, Byung-Ik)
DOI https://doi.org/10.5370/KIEE.2013.62.7.1033
Page pp.1033-1037
ISSN 1975-8359
Keywords Third-winding ; SCR ; SFCL ; Superconducting element ; Line-to-ground fault
Abstract Coercion transformer is commonly used in the electrical grid which in three phase of distribution system. The accident of the electrical grid is divided into a single, a double, a third line-to-ground faults and a double, a third line-to-line faults. A single line-to-ground fault accounts for nearly 75[%] among them. In this research, when a Superconducting Fault Current Limiters (SFCL) was applied to the three phase power system, operation in a single line-to-ground fault and limiting characteristics of fault current according to turns ratio of third winding were analyzed. When a single line-to-ground fault happened, secondary winding's circuit was open. Then third winding's circuit with a SFCL was closed. So fault current was limited by diverted circuit. At this time, we could find out that size of the limited fault current could be changed according to third winding rate. We confirmed that limiting operation of the fault current was carried out within one-period. These results will be utilized in adjusting the size of the SFCL.