Title Comparison of The Attenuation Measurement Methods for Electromagnetic Partial Discharge Signal in 25.8 kV Gas Insulated Switchgear
Authors 구선근(Goo, Sun-Geun) ; 한기선(Han, Ki-Sun) ; 곽주식(Kwak, Joo-Sik) ; 주형준(Joo, Hyung-Jun) ; 정문규(Jeong, Moon-Gyu)
DOI https://doi.org/10.5370/KIEE.2015.64.9.1281
Page pp.1281-1287
ISSN 1975-8359
Keywords GIS ; UHF ; sensor ; partial discharge ; attenuation ; pulse ; spectrum analyzer
Abstract We report the characteristics and differences of two types of attenuation measurement methods for electromagnetic partial discharge signal in GIS. The pulse method is to measure the attenuated waveforms in time domain and coverts them into frequency domain to get the attenuation spectra of given GIS section. This method simulates the real partial discharge signal. The frequency swept continuous wave method can obtain attenuation spectra directly so that it gives attenuation with low noise floor and simplicity. We show that both methods are effective and exchangeable because the attenuation results measured by two methods have similar trends