Title A Synchronization Control Method for SVC to Address Modern Power Loads in Three Phase Four-wire Systems
Authors 임종호(Jong-ho Lim) ; 이현재(Hyun-jae Lee) ; 손진근(Jin-geun Shon) ; 박주헌(Joo-heon Park)
DOI https://doi.org/10.5370/KIEE.2026.75.4.935
Page pp.935-941
Keywords Static Var Compensator; Thyristor Firing Angle Control; Capacitive Load; Capacitive Power Factor; Power Factor Improvement
Abstract This paper presents a synchronous control method for a thyristor-controlled reactor (TCR) applied to a three-phase power system and verifies its power factor correction performance. To this end, the structure of a three-phase four-wire power system is analyzed, and a synchronization-based control strategy suitable for this system is developed. The proposed method is implemented using a Y-connected TCR, and its effectiveness is evaluated through both simulation and hardware experiments. The simulations were conducted using PSIM, while the hardware experiments were performed with a capacitive load configured using AC capacitors to create a leading power factor condition. The results confirm that the proposed synchronous control-based TCR improves the power factor effectively in a three-phase four-wire system.